Acid cleaner is a specially formulated acid cleaner for use in descaling boilers, economizers, cooling jactets, condensers, heat exchanger. This product is a combination of surfactants, acids, inhibitors and penetrants that provide excellent results for light or heavy descaling jobs. The special inhibitors permit use on iron and steel components safely.

General specifications

Appearance........................................................................... red brown liquid

Density at 25℃(77℉)......................................................... 1.11±0.05 g/ml

PH10%)............................................................................2.0

Treatment and feeding requirements

Drain units and where loose deposits were possible away. Should the surfaces be coated with oil or grease, a precleaning is recommended using degreaser. After precleaning, drain and flush with water. Ensure plant is fully ventilated to allow gases released by reaction to escape.

Apply the acid cleaner, diluted from 14 or 110 with water according to type of deposits to be removed. The concentration may be determined by testing samples of deposit with various dilutions of acid cleaner.

Ensure adequate movement within the unit preferably by means of a circulating pump to remove spent acid from the metal surfaces. Where possible, raise the temperature up to 65 by steam coil to a circulating tank.

When solution is sufficiently acid, to properly dissolve scale, the solution will be a gold color. The initial dose is sufficient to obtain the acidity required to procure this color. No additional acid cleaner is required as long as the solution remains gold in color.

As the scale is dissolved and the solution becomes less acid, the solution will turn green. When this occurs, the solution is no longer sufficiently acid to properly dissolve scale and additional acid cleaner should be added. The additional acid cleaner should turn the solution gold again.

Safety precautions

This product is harmful in nature. Precautions should be taken to avoid contact with skin and eyes, inhalation of fumes and mixture with caustic materials.

Packing and handling

Acid cleaner is a liquid packed in non-returnable drums. It can be handled and stored in polyethylene, polypropylene, and other resistance plastics.