TDW /S Once Through Water Boiler

Type S005 S010 S015 S020 S025 S030 S040 S050 S060 S070 S080 S100
Characteristic Max. working pressure
Kg/cm2
10
Teat pressure
Kg/cm2
16
Heating output
Kcal/h
50000 100000 150000 200000 250000 300000 400000 500000 600000 700000 800000 1000000
Water produced (10℃~60℃)
GAL/h
 250
500 
750 1000 1250 1500 2000 2500 3000 3500 4000 5000
Water capability
GAL
17 21 21 29 34 34 66 66 66 66 66 66
Heating surface area m2 2.1 3.4 3.4 4.8 7.5 7.5 9.9 9.9 9.9 9.9 9.9 9.9

Pipe size

Fuel oil inlet inch 1/4" 1/4" 1/4" 1/4" 1/4" 1/4" 1/2" 1/2" 1/2" 1/2" 1/2" 1/2"
Gas inlet mm 20 20 20 25 40 40 40 50 50 50 50 50
Cooling water inlet inch 1-1/2" 1-1/2" 1-1/2" 1-1/2" 2" 2" 3" 3" 4" 4" 4" 4"
Hot water inlet inch 1-1/2" 1-1/2" 1-1/2" 1-1/2" 2" 2" 3" 3" 4" 4" 4" 4"
Safety valve inch 3/4" 3/4" 3/4" 3/4" 1" 1" 1" 1-1/2" 1-1/2" 1-1/2" 2" 2"
Chimney mm 100 150 150 200 250 250 300 300 300 300 300 300
Burner Fuel oil combustion way Forced-draft pressurized atomizing
fuel oil consumption Diesel Kg/h 5.75 11.5 17.25 23 28.75 34.5 46 57.5 69 80.5 92 115
Heavy oil Kg/h NA 29.75 35.7 47.6 59.5 71.4 83.3 95.2 119
Gas combustion way Forced-draft mix combustion
Gas consumption LNG Nm3/h 5.85 11.7 17.55 23.4 29.25 35.1 46.8 58.5 70.2 81.9 93.6 117
LPG Kg/h 4.8 9.6 14.4 19.2 24 28.8 38.4 48 57.6 67.2 76.8 96

Dimensions

Depth mm 620 872 872 872 907 946 1190 1190 1190 1788 1845 1845
Width 530 1230 1230 1230 1326 1500 1834 1834 1834 1631 1723 1723
Height 1590 1844 1844 2024 2029 2145 2046 2046 2046 2046 2120 2330

1. The fuel consumption is calculated according to low heat value:
  Diesel:HL=8,600Kcal/L   Heavy oil:HL=10000Kcal/L
  LNG:HL=8900Kcal/kg    LPG::HL=10500Kcal/kg
2. The pressure of gas entrance:
 LNG - 200mmAq       LPG - 280mmAq
3. We reserve the right to make necessary modification and adjustment in specification and dimensions, etc. without further notification in case of improvement in equipment or other causes.